Three phase ups systems 8.0 help, Help – OnLine Power Battery Backup System User Manual

Page 66

Advertising
background image

OLP

Three Phase UPS Systems

8.0

HELP

8-1

8. HELP

Followings are some abnormal situations frequently asked and common solution is

offered for trouble-shooting.

Abnormal

Description & Checkpoint

Solution

The rectifier breaker is not switch on.

Switch on the rectifier
breaker.

The input voltage is not correct (out of
the normal range).

Connect the right AC
source.

The phase sequence of AC input is
incorrect, input rotation error, and the
LCD will display warning message
“RECT PHASE ERROR” in the

STATUS/WARN menu (MAIN menu →

SELECT menu → STATUS/WARN

menu). ROTATION ERROR LED on
left side of the front panel will also
light.

Correct the R.S.T. phase
sequence. Generally, to
exchange any two phases
connection can solve this
problem.

(1) AC input

is correct, but
rectifier does
not operate
and RECT AC
FAIL LED
lights up.

If the abnormality cannot be corrected
when the solution actions have been
taken.

Refer to PCB LED
Detecting Guide and
check the 3C PCB.

(2) The UPS

shuts down
under AC
mains failure.

The battery fuse (breaker/holder/dis-
connector) has not been closed.

Close the battery fuse
breaker/holder/dis-
connector.

The reserve breaker has not been closed
(switched on).

Close the reserve breaker.

(3) No power

supply for
UPS control
circuit and
LCD cannot
display.

3B PCB has problem.

Refer to PCB LED
Detecting Guide and
check the 3B PCB.