TABLE 2-7

PHASE STABILIZER FLOOR LOADING

kVA SIZE

INPUT

VOLTAGE

FLOOR LOADING

lbs/sq ft (kg/sq m)

kVA SIZE

INPUT

VOLTAGE

FLOOR LOADING

lbs/sq ft (kg/sq m)

15

208

82 (399)

150

208

134 (513)

480

480

168

(822)

30

208 102

(500)

175

208 155

(597)

480

480

125

(480)

50

208 143

(701)

200

208 181

(696)

480

480

134

(513)

75

208 184

(899)

225

208 206

(778)

480

480

142

(546)

100 208

112

(431) 250 208

220

(845)

480 192

(934)

480 164

(629)

125 208

121

(464) 300 208

259

(994)

480 161

(788)

480 172

(662)

400

480

188

(724)

TABLE 2-8

SINGLE PHASE POWER REG FLOOR LOADING

kVA SIZE

INPUT VOLTAGE

FLOOR LOADING lbs/sq ft (kg/sq m)

10 208

97

(35.3)

480

20 208

111

(40.2)

480

30 208

139

(50.4)

480

50 208

194

(71)

480

75 480

236

(86)

100 480

278

(101)

2-3

CABLE ACCESS AND FLOOR LAYOUT

2-3-1 Cable

Access

Cable access to the Power-Reg, Ultra-Reg and Phase Stabilizer, sizes 100 to 400 kVA, is through a 4” diameter
hole in the right and left sides of the unit throught which the input and output cables can be passed. Cable
access to the Phaze Stabilizer, sizes 15 to 75 kVA, and the Constant Power 18 is through an opening in the left
and right side of the unit. See Illustrations 2-1 and 2-2.