Online power, Danger – OnLine Power Phase Stabilizer User Manual

Page 40

Advertising
background image

OnLine Power

6002-032 REV H

3-1

SECTION 3 - INSTALLATION

3-1 INSTALLATION
Install unit using the procedures in this section. Final installation must be in accordance with NEMA standards
and conform to local electrical codes as appropriate.

3-1-1 Unpacking
Unit is shipped on a pallet, secured with metal bands and can be handeled using a fork lift or pallet jack.

DANGER!!

CUT METAL BANDS CAREFULLY. THEY ARE UNDER TENSION AND MAY
CAUSE INJURY.

1.

Position the container away from walls or other obstructions.

2.

Cut metal shipping bands.

3.

Remove cardboard cover. Avoid puncturing the cardboard cover with sharp objects which may damage the
surface of the unit.

4.

Remove the unit from the pallet.

• Power-Reg, Ultra-Reg and Phase Stabilizer (100- 400 kVA) can be removed using fork lift.

• CP 18 and Phase Stabilizer (15 - 75 kVA) come with integral casters and are packed with a wooden

ramp. Secure ramp from slipping and roll unit off pallet. Secure ramp to pallet before rolling unit down
ramp.

• Single phase Power-Reg (10-100KVA) can be removed using forklift.

5.

Remove protective plastic film.

6.

Inspect unit for damage per Section 3-1-2, Inspection.

7.

Move unit to installation site.

8.

Before final positioning of unit, verify that all cable routing conduit and raceway is positioned
properly.

CAUTION

unit weighs from 400 lbs (181 kg) to 3,500 lbs (1,588 kg) including the packaging. Use care
when rolling unit with integral casters. Plywood or steel plates may be used to distribute
weight and protect floor surface from overload damage.