Remko rvs...h (inox) – REMKO RVS 60 H User Manual

Page 10

Advertising
background image

Target value cooling mode

Programming target values

The target value cooling (r 01) and the actual (hysteresis) cooling (r 02)

can be displayed and changed under the menu item “-r-” without the

use of a password.

With the Key-Pad

▲ or ▼ the value can be changed within limits.

r 01 = 12.0 °C

Target value cooling mode (factory setting)

r 02 = 2.0 °C

Hysteresis cooling mode (factory setting)

Minimum target value cooling mode

10.0 °C

Maximum target value cooling mode

28.0 °C

Target value heating mode

The target value heating (r 03) and the hysteresis heating (r 04) can be

displayed and changed under the menu item “-r-” without the use of

a password.

With the Key-Pad

▲ or ▼ the value can be changed within the limits set

in the factor (r15 + r16).
r 03 = 40.0 °C

Target value heating mode (factory setting)

r 04 = 2.0 °C

Hysteresis heating mode (factory setting)

Minimum target value heating mode

15.0 °C

Maximum target value heating mode

45.0 °C

Password

Password

Display

Display

Submenu

Submenu

Submenu

Submenu

short-term

short-term

min. 5 sec.

+

...

repeated

short-term

short-term

short-term

short-term

Target value cooling

Target value cooling

old target value

old target value

new target value

new target value

short-term

short-term

min. 5 sec.

+

...

...

repeated

short-term

short-term

short-term

short-term

REMKO RVS...H (INOX)

10