Remko rvs...h (inox) – REMKO RVS 60 H User Manual

Page 22

Advertising
background image

Connection of the
medium lines

The connection of the lines

on-site takes place on the front

side of the unit.

For the purpose of servicing,

connections must be equipped

with shut-off valves and valves

for hydronic balancing.

Additional automatic bleed

valves are to be provided in the

supply and return at the instal-

lation's highest point.

The medium lines must not

exert any structural load on the

unit.

The line connections may not

generate any thermal or

mechanical stress on the unit.

If necessary, the lines should be

independently supported.

If the unit is at first to be operated

with only a part of the

entire system, the medium

flow volume for the missing

system components are to be

simulated using the volume

control valve.

The pipe size must not restrict

the minimum medium flow.

Installation of the safety valve

The standard safety valve is not in-
stalled. Position the valve as shown
in the illustration and carry out
the correct installation of the drain
line. Local disposal
regulations must be observed if
glycol is used.

Pipe routing
RVS 60H / RVS 75H

free pipe

routeing

possible

free pipe

routeing

possible

no pipe

routeing possible

RVS 100H / RVS 150H

Necessary system components

No pipe r

outeing possible

No pipe r

outeing possible

No pipe routeing

possible

A permanent large flow volume
must be ensured to realise the
minimum medium flow.

!

CAUTION

Position safety valve

RVS 60H to RVS 150H with medium storage tank (hydr. compensator)

RVS 60H to RVS 150H

Diagram of the System components

Legend:

1

Flow switch

2

Dirt trap

3

Shut-off valve

4

Compensator

5

Pressure gauge

6

Emptying

7

Automatic bleeding valve

8

Safety valve

1

7

8

8

6

9

9

5

13

13

4

4

12

14

15

3

3

11

11

2

10

10

1

7

8

6

9

5

13

4

4

12

14

15

3

3

11

2

10

10

9

Circulation pump

10 Valve for hydronic balancing

11 Diaphragm expansion vessel

12 Plate heat exchanger (evaporator)

13 Medium storage tank

14 Probe medium intake

15 Probe medium outlet

shippment

shippment

provided by the customer

provided by the customer

REMKO RVS...H (INOX)

22

Advertising
This manual is related to the following products: