Remko rvs...h (inox) – REMKO RVS 60 H User Manual

Page 16

Advertising
background image

Fault

Code

Possible cause

check

Remedial measures

The unit

does not

start or

switches

itself

off.

Mains failure

Does all other electrical equip-

ment function correctly?

Check voltage and if necessary

wait until turned on again.

Unit's breaker/mains switch

turned off

Is voltage available to the unit?

Switch on unit's breaker/ main

cycle breaker.

Wait time too short

Is the compressor icon flashing?

Plan for longer wait period.

Mains current has incorrect

direction of rotation.

Has the phase sequence relay

switched?

Change direction of rotation.

Controller is not working

Is the icon for cooling mode, heating

mode or Stand-By mode illuminated?

Energise and

select operating mode.

Medium intake temperature or

parameter setting wrong

Check setting.

Change setting.

No alarm / fault

Check the contact "external

enable"

Open / close

the contact being used.

E1

Medium intake probe defective

Check resistance at B1

Replace defective probe.

E2

Medium outlet probe defective

Check resistance at B2

Replace defective probe.

E3

Condenser probe defective

Check resistance at B3

Replace defective probe.

E4

Outdoor temperature probe

Cooling cycle pressure transducer

defective

Check resistance/voltage at B4

Replace defective tranceducer.

HP1

High pressure fault

Compressor relay switched on?

Have checked by a specialist.

High pressure fault

Are the fans turning?

Is the condenser's air intake free

of obstacles?

Have checked by a specialist.

High pressure fault at pressure

tranceducer PT

Is the value at B4 greater than

40 bar?

Have checked by a specialist.

LP1

Low pressure fault

Is the pressure in the cooling

cycle OK?

Have checked by a specialist.

Ht

Excessive temperature medium

intake

Is the return temperature greater

than 50°C?

Reduce temperature of the

medium

Excessive temperature con-

denser

Are the fans turning?

Is the condenser's air intake free

of obstacles?

Have checked by a

specialist.

Excess temperature condenser

Have the operating temperatures

been exceeded?

Shut down the system.

A1

Antifreeze alarm has

responded

Is the supply temperature greater

than or less than 4°C?

Increase return temperature,

Increase medium flow volume,

Set frost protection temp..

Medium volume in the system

too low

Has the minimum medium vol-

ume been complied with?

Comply with minimum medium

volume e.g. in the reservoir.

FL

Differential switch /

Flow switch

has responded

Are the following points OK:

- Medium flow volume

- No air in the medium lines

- Output of the circulation pump

- Does the flow switch operate

- Shut-off devices open

- Medium pressure to low

Have checked by a

specialist.

D1

Fault defrosting

Maximum defrosting duration

exceeded

Have checked by a specialist.

Hc1

Compressor 1 maintenance

Maintenance interval compressor

1 has been reached.

After maintenance by a special-

ist reset of the operating hours

see chapter "Querying the

operating status".

Malfunctions

REMKO RVS...H (INOX)