REMKO Multi-talent Plus User Manual

Page 15

Advertising
background image

Hot water

Designation

Value range

Factory setting

Description

1xhot water

On/Off

Off

The tank is only enabled for a one time loading
(= ON) (e.g. for showering outside of hot water times).

Loading begins if the T-WW 1 target temperature has been
undercut in the amount of the switching hysteresis (see spe-
cialist

hot water

hysteresis WW).

T-WW 1 target

10°C-70°C

50°C

Setting the desired hot water temperatures for the hot water
programme's 1st, 2nd and 3rd enabling times (see time
programme

hot water).

T-WW 2 target

10°C-70°C

50°C

T-WW 3 target

10°C-70°C

50°C

BoB value

0.0K-70.0K

0.0K

Power saving function for solar or solid fuel boiler (operation
without burner).

The burner is activated if the current hot water temperature
in the amount of the set value here + switching hysteresis
(see specialist

hot water

hysteresis WW) has fallen

below the set hot water target temperature.

Circ with WW prog

On/Off

Off

Activating the circulation pump.

The circulation pump runs when hot water is enabled
(= ON), the circulation programme (see time programme

circulation programme) has no impact.

Anti-legionella

On/Off

Off

Activating the anti-legionella function.

With every 20th heating or at least once a week (on
Saturdays at 01:00) the tank is warmed to 65°C (= ON).

It is possible to set a separate anti-legionella function e.g.
by means of the 3rd hot water enabling time (see time
programme

hot water).

Be submitted to activation of anti-legionella program must
usually electric heating thermostat to 65 °C.

Heating circuit 1/2

Designation

Value range

Factory setting

Description

Operating mode

----

Standby

Automatic 1+2

Summer

Heating

Reduction

----

Setting the operating mode for the respective heating circuit.

!

CAUTION

If an operating mode is set here outside of "----", this
operating mode will always apply for the respective heating
circuit regardless of the operating mode setting in the main
menu. (see page 7). This setting possibility is intended for
the use of a remote control.

T-room target 1

5.0°C-40.0°C

20.0°C

Setting the desired room temperature for the
1st, 2nd and 3rd enable time of the active heating
programme for the selected heating circuit.

T-room target 2

5.0°C-40.0°C

20.0°C

T-room target 3

5.0°C-40.0°C

20.0°C

T-reduction

5.0°C-40.0°C

15.0°C

Setting the desired room temperature during night reduction
(time between heating periods, see time programme

heating circuit 1/2 prog 1/2).

Adjustable values can vary depending on the function selected for the heating circuit.

Level 4 - USER - Description of parameters and settings - continued

15