Remko heat pump manager – REMKO Multi-talent Plus User Manual

Page 6

Advertising
background image

REMKO Heat Pump Manager

Heating curves

The heating curve is used for the
purpose of assigning the building
and appropriate target supply tem-
perature in accordance with the
outdoor temperature. The heating
curves 0.2 to 0.8 have their base
point at 20°C and are intended
for surface heating. The heating

curves 1 to 3 have their base point
at 27°C are therefore appropriate
for radiator heating (steel radia-
tors). The heating curve is easiest
to set at outdoor temperatures
below 5 °C. Changing the heating
curve setting must be carried out
in small steps and in larger time

intervals (at least 5 to 6 hours),
because the system must first ad-
just to the new values after every
change in the heating curve.

Outdoor temperature in °C

Tar

get supply temperatur

e in °C

6

Advertising