Designation

Value range

Factory setting

Description

Operation HCP

Standard

Heating limits

only time prog

Continuous

operation

Standard

Setting the operating mode for the pumps.

The circulation pumps are shut off if there is no heating

requirement. Mixers are closed at the same time (the heating

circuit is shut off).

Standard (standard circulation pump switching).

Room managed regulation (OFF: Room temperature > set

room target value + 1K).

Weather managed regulation in heating mode (OFF:

Outdoor temperature > set room target value).

Weather managed regulation in reduction mode (room im-

pact = 0; OFF: The switching off takes place during the tran-

sition to reduction mode. The pump operates after switching

on with ON: Room temperature < room target value; room

impact = OFF; OFF: Supply target temperature < 20°C.)
Heating limits (Pump switching based on heating limits).

Heating period (OFF: Outdoor temperature < set heating

limit day).

Reduction period (OFF: Outdoor temperature < set heating

limit night).
only time prog (Pump switching based on heating pro-

gramme).

Heating period (ON, heating circuit is free).

Reduction period (OFF, heating circuit is locked).
Continuous operation.

The pump runs continuously for 24h. The heating circuit is

continuously free.

Mixer Open

5,0-25,0

7,0

Setting the speed with which the mixer opens in the event
of a control deviation (mixer dynamic opening).

The control deviation is entered in Kelvin where the mixer
opens without interruption.

Small values lead to fast operation of the mixer and can lead
to vibrations.

Mixer Closed

5,0-25,0

7,0

Setting the speed with which the mixer closes in the event of
a control deviation (mixer dynamic closing).

The control deviation is entered in Kelvin where the mixer
closes without interruption.

Small values lead to fast operation of the mixer and can lead
to vibrations.

Max T-supply

10.0°C-110.0°C

55.0°C

Setting the maximum supply temperature for the selected
heating circuit.

The calculated supply target temperature for the heating
circuit is limited by the set maximum supply temperature
(overheating protection).

The heating circuit pump for the direct heating circuit is only
switched off if the [sensor 08] exceeds the temperature set
here by 8K.

The heating circuit pump switches on again if the
temperature [sensor 08] falls below the temperature
(Max T-supply+5K).

Heating circuit 1/2-continued

Level 4 - SPECIALIST - Description of parameters and settings - continued