REMKO Multi-talent Plus User Manual

Page 33

Advertising
background image

Heat pump

Designation

Value range

Factory setting

Description

Max T-return WP

30.0°C-110.0°C

60.0°C

Setting the system's maximum return temperature [sensor 17].

All of the heat pumps in the system will be shut off once the
temperature set here has been reached.

The heat pumps will be switched on again if the return tem-
perature has fallen below the value set here by 5K.

Min T-return WP

0.0°C-20.0°C

0.0°C

Setting the system's minimum return temperature [sensor 17].

All of the heat pumps in the system will be shut off if the
temperature set here is undercut.

The heat pumps will be switched on again if the return tem-
perature has risen above the value set here by 3K.

Max TA WE

-20.0°C-40.0°C

-5.0°C

or -3.0°C

Setting the bivalence point.

The 2nd heating appliance will be enabled if the outdoor
temperature is colder than this setting.

Min TA WP

-30.0°C-10.0°C

-20.0°C

Setting the minimum bivalence point.

If the outdoor temperature falls below the value set here, all
heat pumps will be locked and the system will operate only
with conventional heating appliances.

Designation

Value range

Factory setting

Description

Sequence mode

WE sequence 1+2

Chronological

1/2 switch

Rotating

Sorting

WE sequence 1

• Only WE sequence 1.

• Only WE sequence 2.

Chronological (switch between sequence 1 and 2 in accord-
ance with operating hours of the first WE in the active sequence).

1/2 switch (switch for heating appliances with different
nominal output: With the connection of the 2nd WE, the
first WE is taken out of operation until the next connection).

Rotating (the first WE in the sequence is put in the last
position in the current sequence at the end of the sequence
switch period).

Sorting (new WE sequence by means of automatic sorting
by operating hours for a sequence change).

Sequence change

00 h-800 h

00 h

See description specialist

heating appliances.

Clock inhibition

00 Min.-120 Min.

00 Min.

See description specialist

heating appliances.

For the operation of heat pumps, various protection functions (e.g. return temperature monitoring) and functions
for effective operation (monovalence/bivalence mode) are necessary and can be set or activated here (only for
the selection WE 1 type = 07 (heat pump) (see specialist configuration)).