REMKO Heat Pump Manager

System selection

12 basic hydraulic configurations

are provided in the heat pump

manager which can be pulled up

with the system selection and ap-

plied in the controller.

Pulled up with the system selection

and applied in the controller.

The system selection was decided in
accordance with the following criteria:

1. by type of heat pump

- only heating series:

CMF 80, CMF 140

- Heating/cooling series:
CMF 90/150/120/160,

CMT 100/150/120/160
CMF 120/160

System
selection

Functions

1

Basic hydraulics for the functions “Heating and hot water”, single energy-source mode, 1 supple-
mental electric heating, bivalence point -5°C

2

not for heat pumps with heating meters

3

not for heat pumps with heating meters

4

not for heat pumps with heating meters

5

not for heat pumps with heating meters

6

Heating/cooling version, single energy-source mode, 1 supplemental electric heating,
Bivalence point -5°C

7

Heating/cooling version, single energy-source mode, 1 supplemental electric heating, solar system,
bivalence point -5°C

8

not for heat pumps with heating meters

9

not for heat pumps with heating meters

10

Heating/cooling version, bivalent mode, bivalence point -3°C

11

Heating/cooling version, bivalent mode, solar system, bivalence point -3°C

12

Heating/cooling version, bivalent mode with solid fuel + option for 1 supplemental electric heating,
bivalence point -3°C

2. by operating mode

- single energy source

operation (supplemental
heating is a supplemental
electric heater)

- bivalent mode (supplemental

heating is a boiler)

3. by special case

- integration of solar systems

- integration of solid fuel boilers

The following pages show a selec-
tion of these basic hydraulic con-
figurations with the corresponding
basic programming list.

In any case, during commissioning,
assign one of the basic hydraulic
configurations via the menu item
system selection to the “On-site-
system”. Take special care that
the system you select is as near as
possible to system installed on-
site. The location of the sensors is
especially important. Please orient
yourself on the system diagram for
the selected system.

Heating circuit 2 and hot water are recognised by the connected sensor. The relevant menus are hidden if
no sensor is connected.
The systems 2, 3, 4, 5, 8 and 9 were programmed for the equipment type CMF 80/140 and cannot there-
fore be selected for heat pumps with heating meters!

NOTE