Remko heat pump manager – REMKO Multi-talent Plus User Manual

Page 26

Advertising
background image

REMKO Heat Pump Manager

Configuration - continued

Designation

Value range

Factory setting

Description

WE BUS

00-05

05

00 = Relay (switching WE).

01 = CAN-BUS (cascade switching).

02 = eBUS (WE without temperature controller, default
modulation depth, cascade modulating).

03 = eBUS (WE with temperature controller, default target
temperature T-WE target).

04 = 0-10V (default target temperature T-WE target,
burner relays are controlled in parallel).
Only for regulation type 01, 02, 03, 07.
Sensor 08 must be connected.

05 = 0-10V (default modulation depth).
Only for regulation type 02 or 06.

WE 2 type

(Output A7

enable cooling)

00-22

08

Not active for WE 1 with two stage burner.

00 = no second WE.

01 = Single stage WE (switching).

07 = Heat pump.

08 = Cooling 1.

09 = Cooling 2.

20 = Solid fuel boiler (supplemental not controllable WE).

21 = Collector pump

22 = Pump for WE 1 (e.g. supplemental WE for cascades).

WE 2 tank

00-03

00

Only active if WE 2 type as solid fuel boiler was selected.

Start-up release:
ON: T-WE 2 > Min T-WE 2.
OFF: T-WE 2 < [Min T-WE 2-5K].

00 = Heating in countercurrent with collector (no tank)
[sensor 08].
ON: T-WE 2 > [T-collector+Hyst burner 2+5K].
OFF: T-WE 2 < [T-collector+Hyst burner 2].

01 = Heating in countercurrent with buffer tank [sensors
01, 03].
ON: T-WE 2 > [T-buffer O+Hyst burner 2+5K].
OFF: T-WE 2 < [T-buffer+Hyst burner 2].

02 = Heating in countercurrent with WW tank [sensor 06].
ON: T-WE 2 > [T-WW+Hyst burner 2+5K].
OFF: T-WE 2 > [T-WW+Hyst burner 2].

03 = Heating in countercurrent with tank 3 (swimming
pool) [sensor 15].
ON: T-WE 2 > [T-tank 3+Hyst burner 2+5K].
OFF: T-WE 2 < [T-tank 3+Hyst burner 2].

Level 4 - SPECIALIST - Description of parameters and settings - continued

26

Advertising