8  Configuration

SMA Solar Technology AG

52

WB3-5TL-21-IA-en-10

Installation Manual

8.5 Changing the DC Critical Voltage for Feed-in to the

Power Distribution Grid

It is possible to change the default setting for the critical voltage to end and/or start feed-in.
Requirement:

☐ A communication product that is appropriate for the type of communication used must be

available.

Changing the critical voltage to end feed-ing

If the default values for ending feed-in are not in the range of the set polynomial curve, you must adjust
the critical voltages to the zero-crossing of the power-voltage characteristic curve with the x axis. By
doing so, you achieve optimum start-up behavior for the plant.

Figure 14: Power-voltage characteristic curve of a small wind turbine system indicating the default value for

critical voltage to end feed-in and the zero-crossing of the curve with the x axis (example)

1. Select the parameter Critical voltage to end feed-in or Upv-Stop and set the desired value.
2. Save setting.