SMA WB 3000-21 Installation User Manual

Page 63

Advertising
background image

SMA Solar Technology AG

11  Troubleshooting

Installation Manual

WB3-5TL-21-IA-en-10

63

701

Frq. not permitted
Check parameter

The power frequency is not within the permissible range.
The inverter has disconnected from the power distribution
grid.
Corrective measures:

• If possible, check the power frequency and observe

how often fluctuations occur.
If there is a high number of fluctuations and this
message is displayed frequently, contact the grid
operator and ask whether they approve a change
of the operating parameters of the inverter.
If the grid operator approves, discuss any changes
to the operating parameters with the SMA Service
Line.

801

Waiting for grid voltage
Grid failure
Check fuse

The AC cable is not correctly connected or the country
data set is not correctly configured.
Corrective measures:

• Ensure that the AC cable is correctly connected

(see Section 6.3.2).

• Ensure that the country data set has been

configured correctly.

• Check fuse.

901

PE conn. missing
Check connection

PE not connected correctly
Corrective measures:

• Ensure that the PE is correctly connected

(see Section 6.3.2).

1001

L / N swapped
Check connection

The connection of L and N is swapped.
Corrective measures:

• Ensure that L and N are correctly connected

(see Section 6.3.2).

1101

Installation fault
Check connection

The connection of L and N is incorrect.
Corrective measures:

• Ensure that L and N are correctly connected

(see Section 6.3.2).

Event
number

Display message

Cause and corrective measures