11  Troubleshooting

SMA Solar Technology AG

66

WB3-5TL-21-IA-en-10

Installation Manual

3701

Resid.curr.too high

The inverter has detected a residual current after brief
grounding of the small wind turbine system.
Corrective measures:

• Check the small wind turbine system for ground

faults (see Section 11.4).

3801 to
3802

DC overcurrent
Check generator

Overcurrent at the DC input. The inverter briefly interrupts
feed-in.
Corrective measures:

• If this message is frequently displayed, ensure that

the small wind turbine system is correctly rated and
correctly connected to the rectifier.

• Ensure that the DC inputs on the inverter are

bridged (see Section 6.4.3).

3901 to
3902

Waiting for DC start
conditions
Start cond. not met

The conditions for the feed-in to the power distribution
grid have not been met.
Corrective measures:

• Wait for stronger wind, if necessary reduce the

critical voltage to start feed-in. To do this, change
the parameter Critical voltage to start feed-in or
A.VStr.

• If this message is frequently displayed at medium

wind conditions, ensure that the small wind turbine
system is correctly rated.

6001 to
6009

Self diagnosis
Interference device

The cause must be determined by the SMA Service Line.
Corrective measures:

• Contact the SMA Service Line.

6101 to
6112

Self diagnosis
Interference device

The cause must be determined by the SMA Service Line.
Corrective measures:

• Contact the SMA Service Line.

6202

Self diagnosis
Interference device

The cause must be determined by the SMA Service Line.
Corrective measures:

• Contact the SMA Service Line.

6301

Self diagnosis
Interference device

The cause must be determined by the SMA Service Line.
Corrective measures:

• Contact the SMA Service Line.

Event
number

Display message

Cause and corrective measures