10  Recommissioning the Inverter

SMA Solar Technology AG

58

WB3-5TL-21-IA-en-10

Installation Manual

3. Place the lower enclosure lid with the 6 screws on

the enclosure and secure with screw 6. Then tighten
all screws with an Allen key (AF 3) in the order 1 to
6 (torque: 2 Nm).

4. Securely plug in the ESS. The ESS must be aligned

parallel to and flush with the enclosure.

5. Switch on the miniature circuit-breaker.
6. Start the small wind turbine system.

☑ The green LED is lit and the display shows the device type, the firmware version, the NetID,

the configured country data set and the display language.

✖ Green LED flashing?

Possible cause of error: The DC input voltage is still too low, or the inverter is monitoring the
power distribution grid.
• If the DC input voltage is sufficiently high and the grid start-up conditions are met, the

inverter starts to operate.

✖ The red LED is lit and an error message and event number appear in the display?

• Eliminate the fault (see Section 11 "Troubleshooting", page 59).