11  Troubleshooting

Installation Manual

WB3-5TL-21-IA-en-10

69

7305

Update RS485i module
failed

Internal error. The inverter continues to feed into the
power distribution grid.
Corrective measures:

• Re-try update.
• If this message is displayed again, contact the

SMA Service Line.

7307

Update BT failed

Internal error. The inverter continues to feed into the
power distribution grid.
Corrective measures:

• Re-try update.
• If this message is displayed again, contact the

SMA Service Line.

7311

Update language table
failed

Internal error. The inverter continues to feed into the
power distribution grid.
Corrective measures:

• Re-try update.
• If this message is displayed again, contact the

SMA Service Line.

7401

Varistor defective

At least 1 of the thermally monitored varistors is defective.
Corrective measures:

• Check the function of the varistors

(see section 11.5).

7508

External fan fault

The external fan is defective or blocked.
Corrective measures:

• Ensure that the fan is clean.
• Ensure that the external fan is correctly connected.

7701 to
7703

Self diagnosis
Interference device

The cause must be determined by the SMA Service Line.
Corrective measures:

• Contact the SMA Service Line.

8001

Derating occurred

The inverter has reduced its power output for more than
ten minutes due to excessive temperature.
Corrective measures:

• If this message is frequently displayed, clean the

cooling fins and air ducts (see Section 11.3).

• Ensure that the inverter has sufficient ventilation.