3.0 Installation

IMPORTANT: AC - GROUND CONNECTION

(remove this green wire if the neutral is bonded

to ground either at the generator or grid source)

AC NEUTRAL IN
(from neutral of
generator or grid)

AC LEG 1 IN
(from L1 side of
generator or grid)

AC LEG 2 IN
(from L2 side of
generator or grid)

GROUND BUSBAR

(inverter’s input and

output AC GROUND)

GROUND BUSBARS

(from generator/grid

ground and to AC

load panel ground)

IN

PU
T

TO

IN

V

ER
TER

S

INVERTER

GROUND

O

U

TPU

T

T

O

IN

VER

TE
R

LO
A

D

S

LOADS &

GEN/GRID

GROUND

IN

PU
T

FR
O

M

G

EN
/G

R

ID

AC Connections (MPDH-30D Models)

INV HOT 1 OUT

(from each inverter’s

AC HOT 1 output)

INV HOT 2 OUT

(from each inverter’s

AC HOT 2 output)

INV NEUTRAL OUT

(from each inverter’s

AC NEUTRAL output)

O

U

T

PU
T

FR
O

M

IN

VE
R

TER

INV NEUTRAL IN*

(to each inverter’s

AC NEUTRAL input)

INV HOT 1 IN

(to inverter 2

AC HOT 1 input)

INV HOT 2 IN

(to inverter 2 AC

HOT 2 input)

INV HOT 1 IN

(to inverter 1

AC HOT 1 input)

INV HOT 2 IN

(to inverter 1 AC

HOT 2 input)

AC LEG 1 OUT

(to main breaker on L1

side in AC load panel)

AC LEG 2 OUT

(to main breaker on L2

side in AC load panel)

AC NEUTRAL OUT

(to NEUTRAL busbar

in AC load panel)

* The INV NEUTRAL IN is not required if
MS-PAE inverters are used (the neutrals
are common in these inverters).

Figure 3-19, MPDH-30D AC Wiring Connections