0 installation – Magnum Energy Magnum Panel (MP Series) User Manual

Page 57

Advertising
background image

Page 50

© 2011 Magnum Energy, Inc.

3.0 Installation

DC8A

DC6

DC1

DC2

DC4

DC7

DC5

DC3

DC8B

Figure 3-23, DC Wiring Connection Points for MPDH-30D (DC Side)

DC N

EGATIVE

C

ABLE

C

ONNECTIONS

TO

I

NVERTER

A

DDITIONAL

I

NVERTER

DC

N

EGATIVE

C

ABLE

C

ONNECTIONS

DC G

ROUNDING

E

LECTRODE

C

ONNECTIONS

B

ATTERY

B

ANK

P

OSITIVE

C

ABLE

C

ONNECTIONS

A

DDITIONAL

B

ATTERY

B

ANK

N

EGATIVE

C

ABLE

C

ONNECTIONS

DC P

OSITIVE

C

ABLE

C

ONNECTIONS

TO

I

NVERTER

DC E

QUIPMENT

G

ROUNDING

C

ONNECTIONS

B

ATTERY

B

ANK

N

EGATIVE

C

ABLE

C

ONNECTIONS

DC C

ONNECTIONS

(

UNDER

THE

DC D

ISCONNECT

)

I

NVERTER

DC C

ONNECTIONS

(I

N

AC S

IDE

)

DC1

Inverter’s DC Negative Cable Connections - Cable connections to Magnum inverter’s
DC negative terminal. Electrically connected to the top of the DC shunt.

DC2

Inverter’s DC Positive Cable Connections - Cable connections to Magnum inverter’s
DC positive terminal. Electrically connected to the top of the inverter’s DC disconnect.

DC3

Additional Inverter DC Negative Cable Connections - Provided so that as more invert-
er’s are added, cables can be added and connected to the inverter’s DC negative terminals.

DC4

Battery Bank Negative Cable Connections - DC negative busbar connections (bottom
connection of DC shunt); connect cables to the battery bank’s negative terminal.

DC5

Additional Battery Bank Negative Cable Connections - Provided to connect
additional cables to the battery bank’s negative terminal when additional Magnum
inverters are installed.

DC6

Battery Bank Positive Cable Connections - Bottom of the inverter’s DC disconnect
breaker; connect battery cables to the battery bank’s positive terminal.

DC7

DC Equipment Grounding Connections - These busbars are used as the common
DC equipment ground point for all DC equipment connected in the MP/inverter system.

DC8

DC Grounding Electrode Connections - These are the connection points for the MP/
inverter system to the DC grounding electrode. Use DC8A for #6 to #1/0 AWG wires,
and DC8B for greater than #1/0 AWG wires.

Advertising