4 eight shelf 3000 series switch, 1 power consumption, 2 equipment required – EFJohnson 3000 SERIES User Manual

Page 46: Eight shelf 3000 series switch, Supply lines -20, Average voltage/current/power -20, Bus bar resistance -20

Advertising
background image

SYSTEM RACK

4-20

4.4 EIGHT SHELF 3000 SERIES SWITCH

The system rack is a framework for modules that

consists of up to 8-shelves with 13-slots per shelf. In
each shelf, 12-slots are for function modules and
1-slot is reserved for the power module. The power
supplies for the shelves are located in the lower
portion of the rack framework. The framework also
provides support for interconnection wiring, routed
between shelves, and external devices.

4.4.1 POWER CONSUMPTION

The following tables shows the average voltage,

current and power for each supply voltage per card
(based on loading of 96 cards).

Total watts including TIM-DID is 5.74W.

Excluding the TIM-DID provides a total of 4.3W for
normal modules. The total wattage of the terminal is
found by multiplying the wattage of a module by the
number of modules.

Total Watts x No. of Modules = Terminal Power

The wattage required by the power supply is

found by dividing the total wattage of the terminal by
the efficiency of the power supply (0.7).

Terminal Power

÷

0.7 = Wattage of Power Supply

The BTUs per hour are found by multiplying a known
value (3.6) by the wattage required by the power
supply.

3.6 x Wattage of Power Supply = Btu/Hr.

EXAMPLE:

4.3W x 96 = 413W

413W

÷

0.7 = 590W

3.6 x 590W = 2,123 Btu/Hr

4.4.2 EQUIPMENT REQUIRED

Digital Multimeter, voltmeter resolution to
0.001V.

Transmission test set, HP 3551A.

IBM NT compatible computer, with NetSMM
Call Processing Software.

Two CIMs (023-3039-035)

4.4.3 VERIFY RESISTANCE OF BUS BAR AND

POWER SUPPLY LINES

1. Verify the Power Cables are not connected to a

power source.

2. Verify the Power Supplies are not installed in the

Power Supply shelf.

3. Measure the resistance from point-to-point and

verify the resistance as shown in Table 4-17.

Table 4-16 AVERAGE VOLTAGE/CURRENT/

POWER

Voltage

Current

Power

+5V DC

0.50A

2.50W

+12V DC

0.10A

1.20W

-12V DC

0.05A

0.60W

-48V DC

0.03A*

1.44W

Total

5.74W

* DIDs only.

Table 4-17 BUS BAR RESISTANCE

Ohm Meter Lead Positions

Resistance in

Ohms

From

To

Bus Bar A1-A2

Chassis/Frame

Infinite

Bus Bar A1-A2

B1-B2

Black

0

Bus Bar A1-A2

C1-C2

Red

Infinite

Bus Bar A1-A2

D1

Blue

Infinite

Bus Bar A1-A2

E1

White

Infinite

Bus Bar A1-A2

F1

Green

Infinite

C1-C2 Red

D1

Blue

Infinite

D1-Blue

E1

White

Infinite

E1-White

F1

Green

Infinite

Advertising