Fig.5, Fig.4, Preparation – Sealey SAC3153B User Manual

Page 3: Operation

Advertising
background image

3. PREPARATiON

3.1. remove compressor from packaging and inspect for any

shortages or damage. If anything is found to be missing or

damaged contact your supplier.

3.2.

save the packing material for future transportation of the

compressor. We recommend that you store the packing in a

safe location, at least for the period of the guarantee. then, if

necessary, it will be easier to send the compressor to the

service centre.

3.3.

confirm that the mains voltage corresponds with the voltage

shown on the compressor data plate.

3.4.

Assemble the wheels and swivel castor using the nuts, bolts

and washers supplied (fig.8).

3.5.

the compressor should be operated on a horizontal flat

surface, or one that does not exceed 5° either transversely

(tyres fully inflated to 1.5bar) or longitudinally with chocks

(fig.3), and should be in a position that allows good air

circulation around the unit (see 1000mm nominal).

3.6.

Before using the compressor check the oil level by referring

to the oil sight glass (fig.4c). on a horizontal surface, if the

oil level is not up to the red centre mark it should be further

topped up with recommended oil (see section 5.7). to top up

unscrew plug (fig.4B).

3.7.

screw the back half of a filter unit into the port openings in

each head as shown in (fig.4.A). Place a filter cover over

each threaded rod protruding from the back half of the filter

and secure each with a wing nut. refer also to (fig.7).

fig.4

A

c

drain plug

B

Breather (at rear)

A

fig.5

2

1

4

5

3

6

Ac supply

restart

decompression

tube

switch/motor cable

Pull up (on)

push down (off)

receiver

manifold

regulated supply

non regulated supply

(receiver pressure)

control Panel

and

Ancilliaries

utility brackets

4.3.5. stop the compressor by pushing the switch knob (see fig.5.1)

downwards. the compressed air inside the compressor head

will flow out via the air line tube situated beneath the switch

housing. restart is made easier and prevents the motor from

being damaged.

dO NOT, other than in an emergency, stop

the compressor by switching off the mains power, or by

pulling the plug out, as the pressure relief will not then occur

and motor damage may result upon restart.

When the compressor runs correctly and is stopped correctly

there will be:

(a) A whistle of compressed air when the motor stops,

(b) A protracted whistle (about 20-25 seconds) when the

compressor starts with no pressure in the tank.

4.3.6. the output pressure is regulated by the pressure regulator

(fig.5.2). turn the knob clockwise to increase pressure and

counterclockwise to reduce it. the knob can be locked at any

required setting by tightening the locking ring (fig.5.5) up

against the underside of the knob. to determine the correct

working pressure for any piece of equipment check the

corresponding manual. When the compressor is not being

used set the regulated pressure to zero so as to avoid

damaging the pressure reducer.

note: a) If the motor does not cut in and out, but runs

continuously when using an air appliance, the capacity of the

compressor may be too small for the equipment or tool.

b) the gauge (fig.5.4) indicates the pressure inside the

main tank. the gauge (fig.5.3) indicates the

pressure supplied to the air equipment. should the pressure

in the main tank exceed the pre-set switch (fig.5.1)

maximum, the safety valve (fig.5.6) will activate.

WARNiNG! For this reason dO NOT tamper with, or

adjust, the switch or safety valve.

4.3.7. the compressor is fitted with a reset trip, located in the

connection box on top of the motor. the reset button is on the

side of the box (fig.2). should the trip activate, leave for 1

minute before pressing the button to reset. for possible

causes of trip activation and remedies see section 6

troubleshooting.

WARNiNG! Ensure that you have read, understood and

apply Section 1 safety instructions.

4.1. iMPORTANT. The use of extension leads to connect this

compressor to the mains is not recommended as the

resulting voltage drop reduces motor, and therefore

pump, performance and could damage your compressor.

4.2. Take care when selecting tools for use with the

compressor. Air tool manufacturers normally express the

volume of air required to operate a tool in cubic feet per

minute (cfm). This refers to free air delivered by the

compressor (‘air out’) which varies according to the

pressure setting. do not confuse this with the

compressor displacement which is the air taken in by

the compressor (‘air in’). ‘Air out’ is always less than ‘air

in’ - due to losses within the compressor. 4.3.

STARTiNG THE COMPRESSOR.

4.3.1. Your compressor is fitted with a push/pull type on/off

switch. to turn the compressor "on" pull the switch knob

upwards. to turn the compressor "off" push the knob

downwards. (see fig.5.1)

4.3.2. check that the on/off switch is in the “off” position and

the regulator tap (fig.5.2) is closed (Zero ‘0’ bar).

4.3.3. Plug mains lead into mains supply and start the compressor

by pulling the switch knob (fig.5.1) upwards.

4.3.4. leave the compressor running with no air line or tools

connected, and regulator (fig.5.3) set to maximum pressure

(fully clockwise). make sure that the pressure in the tank

rises and that the compressor stops automatically when the

maximum pressure is reached. this value is written on the

specification plate and shown on the gauge (fig.5.4). this

may take in excess of 5 minutes. the compressor will now

operate automatically. the pressure switch (fig.5.1) stops the

motor when the maximum tank pressure is reached and

restarts it when pressure falls below the minimum threshold

approximately 2bar (29psi) less than the maximum pressure.

4. OPERATiON

Original Language Version

sAc3153B/sAc3203B Issue no: 1 - 01/06/13

© Jack sealey limited 2013

Advertising
This manual is related to the following products: