Connection to the flue pipe, Flue pipe – MCZ Forma Wood 115 User Manual

Page 9

Advertising
background image

INSTALLATION AND USE MANUAL

Chapter 2

page

9

Theoretical notions for installation

Technical service – MCZ S.p.A. all rights reserved - Reproduction prohibited

2.4. CONNECTION TO THE FLUE PIPE

The connection to the flue pipe is a very important element. The

connection must be made with a great deal of care; in the event of

erroneous or anomalous construction, it is extremely difficult to remedy

without damaging the hood liner. In addition, the connection is made in

a part of the stove where temperatures are very high, and for this

reason it is important to use materials that are capable of resisting heat

and also the acidity of the fumes produced by combustion.
Before beginning work, please note the following:

The connection must have a maximum inclination of 45° to

prevent excessive build up of condensation produced in the
initial start-up stages of the closed fireplace and/ or excessive

adhesion of creosote. This also prevents smoke evacuation from

slowing down.

The unions must be made of metal and suitable for the

specific operating conditions of the product and marked

EC (EN1856-2). The use of flexible and extending metal

pipes is not permitted.

The elements of the connection must be perfectly sealed.

The connection to the flue pipe must be neither too long (to

prevent obstructions) nor too short (to prevent smoke leakage).

If metal connecting pipes are used, they must be

insulated with suitable material such as ceramic fibre

matting, to avoid deterioration of the masonry and of

the decorative hood liner.

IMPORTANT!
Any increase in the section of the connecting pipe

must start immediately above the hood of the

fireplace and not along the flue pipe section.

2.5. FLUE PIPE

The flue pipe is a fundamental element in discharging smoke and

therefore must have the following requisites:

be waterproof and thermally insulated.

be made of suitable heat-proof materials that are resistant to

the effects of combustion products and any possible

condensation.

have a vertical arrangement with deviations from the axis of

no more than 45° and without kinks.

must be suitable for the specific operating conditions of the

product and marked EC (EN1856-1, EN1443).

must be suitably sized to accommodate the draught/smoke

disposal requirements necessary for the correct functioning of

the product (EN13384-1).

have an internal section which is preferably circular.

be cleaned if pre-existing and has operated beforehand.

The flue pipe is of primary importance for the correct

functioning and safety of your fireplace stove.

Example of fireplace stove connection

Flue pipe

Hood grille

Smoke

connection

Ceramic fibre

insulation

45° max

Typical diagram of a correctly laid flue pipe
with a chamber including a sealed hatch to
collect and remove solid materials produced
during combustion positioned at the foot of
the external rising section.