Dual Process Input

TWO INPUTS

Two inputs, each separately field selectable:
0-20, 4-20 mA,

±10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)

CHANNELS

Channel A, Channel B, Channel C (Math channel)

PROGRAMMA-
BLE CONSTANTS

Constant P (Adder): -99999 to 999999, default: 0.000
Constant F (Factor): 0.00001 to 999999, default: 1.000

MATH
FUNCTIONS

Name Function Setting
Addition

(A+B+P)*F

Sunm

Difference (A-B+P)*F

diF

Absolute diff.

((Abs(A-B))+P)*F

diFAbS

Average

(((A+B)/2)+P)*F

AvG

Multiplication

((A*B)+P)*F

nmulti

Divide

((A/B)+P)*F

divide

Max of A or B

((AB-Hi)+P)*F

Hi-Ab

Min of A or B

((AB-Lo)+P)*F

Lo-Ab

Draw

((A/B)-1)*F

drAuw

Weighted avg.

((B-A)*F)+A

uw avg

Ratio

(A/B)*F

ratio

Concentration

(A/(A+B))*F

Concen

Note: The F constant can be any value from 0.00001 to
999999. If the value is less than 1, it will have the same effect
as a divider. For example, the average could also be derived
by using (A+B)*F, where F = 0.500.

SEQUENCE OF
OPERATIONS
FOR INPUT
PROGRAMMING

1.

Select Input for A and B

2.

Set up the engineering units for A, B, and C

3.

Set up decimal point for A, B, and C

4.

Scale A & B

5.

Set up the displays for A, B, or C

6.

Select the transfer function for A & B (e.g. Linear)

7.

Select Math function for Channel C

8.

Program constants for Factor (F) and Adder (P).

9.

Program cutoff values for A and B

ACCURACY

±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy
range: 10-100% of calibrated span

TEMPERATURE
DRIFT

0.005% of calibrated span/

°C max from 0 to 65°C ambient,

0.01% of calibrated span/

°C max from -40 to 0°C ambient

SIGNAL INPUT
CONDITIONING

Linear, square root, programmable exponent, or
round horizontal tank volume calculation