Setting the relay operation ( relay ) – Precision Digital PD6060 User Manual

Page 45

Advertising
background image

Model PD6060 Dual-Input Process Meter

Instruction Manual

45

Setting the Relay Operation (relay)

This menu is used to set up the assignment and operation of the relays.
CAUTION! During setup, the relays do not follow the input and they will

remain in the state found prior to entering the Relay menu.

1. Relay

assignment

a. Channel

A

b. Channel

B

c. Channel C (Math channel)
d. Modbus

2. Relay

action

a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm

condition has cleared)

e. Pump alternation control (automatic reset only)
f.

Sampling (the relay is activated for a user-specified time)

g. Off (relay state controlled by Interlock feature)

3. Set

point

4. Reset

point

5. Fail-safe

operation

a. On

(enabled)

b. Off

(disabled)

6. Time

delay

a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)

7. Relay action for loss (break) of 4-20 mA input (ignore, on, off)