Setting Numeric Values

The numeric values are set using the Right and Up arrow buttons. Press
Right arrow to select next digit and Up arrow to increment digit value.
The digit being changed is displayed brighter than the rest.
Press and hold up arrow to auto-increment the display value.
Press the Enter button, at any time, to accept a setting or Menu button
to exit without saving changes.

Increment Digit

Value

Select Next Digit

Accept Setting

0

0

4.000

dis 1

00

4.

000

dis 1

Next

Setting

00

5.

000

dis 1

Reset Menu (reset)

The Reset menu is used to reset the maximum or minimum reading
(peak or valley) reached by the process; both may be reset at the same
time by selecting “reset high & low” (rst HL). The tare value used to
zero the display may be reset by selecting “reset tare” (rst tr).

Control Menu (Contrl)

The Control menu is used to control the 4-20 mA analog output and the
relays manually, ignoring the input. Each relay and analog output can
be programmed independently for manual control. Selecting automatic
control sets all relays and analog output for automatic operation.

A ou t

m a n

C o n t r l

r l y 8

m a n

r l y 1

m a n

a u t o

c o n t r l

m a n

c o n t r l

1

6

.0 0 0

A o u t

o n

r l y 8

o F F

r l y 1

Once Manual mode is initiated on any relay or
analog output, an LED labeled “M” is turned
on. Every few seconds, all LEDs representing
outputs that are in Manual mode, as well as
the “M” LED flash. This process will continue
as long as any output is in manual mode.