Instruction Manual

11

MULTI-POINT
LINEARIZATION

2 to 32 points for channel A and B

PROGRAMMA-
BLE EXPONENT

1.0001 to 2.9999

LOW-FLOW
CUTOFF

0-999999 (0 disables cutoff function)

DECIMAL POINT

Up to five decimal places or none:

d.ddddd

, d.dddd, d.ddd, d.dd, d.d,

or

dddddd

CALIBRATION
RANGE

Input
Range

Minimum Span
Input 1 & Input 2

4-20 mA 0.15 mA
±10 V

0.10 V

An Error message will appear if the input 1 and input 2
signals are too close together.

INPUT
IMPEDANCE

Voltage ranges: greater than 500 k

Ω

Current ranges: 50 - 100

Ω

(depending on resettable fuse impedance)

INPUT
OVERLOAD

Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.

F4 DIGITAL INPUT
CONTACTS

3.3 VDC on contact. Connect normally open contacts
across F4 to COM.

F4 DIGITAL INPUT
LOGIC LEVELS

Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC

Relays

RATING

2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
external; rated 3 A @ 30 VDC and 125/250 VAC resistive
load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads

NOISE
SUPPRESSION

Noise suppression is recommended for each relay contact
switching inductive loads; see page 22 for details.

DEADBAND

0-100% of span, user programmable

HIGH OR LOW
ALARM

User may program any alarm for high or low trip point.
Unused alarm LEDs and relays may be disabled (turn off).

RELAY
OPERATION

Automatic (non-latching)
Latching (requires manual acknowledge)
Sampling (based on time)
Pump alternation control (2 to 8 relays)
Off (disable unused relays and enable Interlock feature)
Manual on/off control mode