Setting up the interlock relay (force on) feature, Act 1, Setup relay – Precision Digital PD6060 User Manual

Page 62: Rly 1, User f1, F on 1, Di 1

Advertising
background image

Model PD6060 Dual-Input Process Meter

Instruction Manual

62

Setting Up the Interlock Relay (Force On) Feature

Relays 1-4 can be set up as interlock relays. To set up the relays for the
interlock feature:
1. Access the SetupRelayAction menu and set the action to off.

Act 1

r l y 1

Off

A c t 1

setup

relay

setup

rly 1

relay


2. In the Advanced features – User menu program any of the digital

inputs to Force On any of the internal relays (1-4).

user

F1

user

F On 1

dI 1

dI 1

user

3. Connect a switch or dry contact between the +5V terminal and the

corresponding digital input (dI-1 to dI-4) terminal.

1

2

3

4

5

6

+5

I1

I2

I3

I4

O1

7

8

O2

O3

9

10

O4

G

DI 1-4

DO 1-4

5 VDC

GND

SW2

SW1

Interlock Relay Operation Example

Relays 1 & 2 are configured to energize (their front panel LEDs are off)
when SW1 & SW2 switches (above) are closed. If the contacts to these
digital inputs are opened, the corresponding front panel LEDs flash
indicating this condition. The processes being controlled by the interlock
relay will stop, and will re-start only after the interlock relay is re-
activated by the digital inputs (switches).