Precision Digital PD6060 User Manual

Page 77

Advertising
background image

Model PD6060 Dual-Input Process Meter

Instruction Manual

77

Analog Output Source

The analog output source can be based on either of the input channels
(Ch-A, Ch-B), the math channel (Ch-C), maximum stored value of either
input channel (Hi-A, Hi-B), minimum stored value of either input channel
(Lo-A, Lo-B), relay set points, or the Modbus input.

Analog Output Calibration

To perform the analog output calibration it is recommended to use a
milliamp meter with a resolution of at least 0.1 µA to measure the output
current. The values saved internally during this procedure are used for
scaling the 4-20 mA output in the Setup menu.

Advertising
This manual is related to the following products: