Precision Digital PD6060 User Manual

Page 71

Advertising
background image

Model PD6060 Dual-Input Process Meter

Instruction Manual

71

Noise Filter Bypass (bypass)

The noise filter bypass changes the behavior of the meter so that small
variations in the signal are filtered out but large abrupt changes in the
input signal are displayed immediately. The bypass value determines
the minimum amount of signal change to be displayed immediately. All
signal changes smaller than the bypass value are filtered or averaged
by the meter. The noise filter bypass may be set between 0.1 and
99.9% of full scale.

Advertising
This manual is related to the following products: