6.3.

POSITION "POWER"

This function permits you to display in real time the RMS value of AC/DC voltage, the peak
and ThdV value of the 3 phase voltages, the waveform of the 3 phase voltages, the RMS
value of AC/DC currents, the peak and Thdl of the 3 phase currents, the waveform of the 3
phase currents. Furthermore, the instrument calculates and displays the value of the
phase and total active powers, the value of the phase and total reactive and capacitive
powers, the value of the phase and total power factors and cos

.


6.3.1. Symbols
The position POWER has two working modes:

 METER
 WAVE


For voltage and current harmonics see paragraphs 6.1.3 and 6.2.3 respectively.

These modes will be described in detail in the next paragraphs.
The symbols used are described below:

Symbol

Description

V1, V2, V3

RMS value of the voltage of phase 1, phase 2, phase 3 respectively

V12, V23, V32, V31

RMS Value of the phase to phase voltages

freq

Network frequency

Phseq

Phase sequence indicator

"123"

correct

"132"

inverted

"023"

null voltage on the black wire

"103"

null voltage on the red wire

"120"

null voltage on the blue wire

"100"

null voltages on the red and blue wires

"020"

null voltages on the black and blue wires

"003"

null voltages on the black and red wires

I1, I2, I3

RMS value of the current of phase 1, phase 2, phase 3 respectively

IN

RMS value of the current of the neutral

Pt, P1, P2, P3

Values of the active power (total, of phase 1, phase 2, phase 3 respectively)

P12, P32

(only for 3 wires measurement) Value of the power measured by the Wattmeter 1-2
and 3-2 respectively (see paragraph 16.3.2).

Qt, Q1, Q2, Q3

Values of the reactive power (total, of phase 1, phase 2, phase 3 respectively)

Q12, Q32

(only for 3 wires measurement) Value of the power measured by the VAR meter
Va1-2 and 3-2 respectively (see paragraph 16.3.2).

St, S1, S2, S3

Values of the apparent power (total, of phase 1, phase 2, phase 3 respectively)

S12, S32

(only for 3 wires measurement) Value of the power measured by the VA meter Va1-
2 and 3-2 respectively (see paragraph 16.3.2).

Pft, pf1, pf2, pf3

Values of the power factors (total, of phase 1, phase 2, phase 3 respectively)

dPft, dpf1, dpf2, dpf3 Value of the cos

(total, of phase 1, phase 2, phase 3 respectively)

Ead, Pd

Values of the Total Active Energy and Active Power On demand respectively

Esd, Sd

Values of the Total Apparent Energy and Apparent Power On demand respectively

Tab. 3: Symbols used in the position POWER

The symbols "i" and "c" stand for reactive powers (Q), power factors (Pf) and cos

(dpf)

respectively inductive and capacitive.