DMIIIS

EN - 35

6.4.2. "METER" mode
On rotating the switch to this position the instrument selects automatically the METER
mode corresponding to one of the below screens according to the settings made as per
paragraph 5.2.

27.09.00 17:35:12

27.09.00 17:35:12

27.09.00 17:35:12

ENERGY

SINGLE PH ASE

Ea1 = 0.000 kWh

Erc1 = 0.000 kVARh

Eri1 = 0.000 kVARh

Es1 = 0.000 kVAh

P1 = 36.38 kW

Q1 = 6.375 kVAR

S1 = 36.94 kVA

Meas Time: 00:00:00

ENERGY

THREE PHASE

Eat = 0.000 kWh

Erct = 0.000 kVARh

Erit = 0.000 kVARh

Est = 0.000 kVAh

Pt = 36.38 kW

Qt = 6.375 kVAR

St = 36.94 kVA

Meas Time: 00:00:00

ENERGY

THREE PHASE

Eat = 0.000 kWh

Erct = 0.000 kVARh

Erit = 0.000 kVARh

Est = 0.000 kVAh

Pt = 167.7 kW

Qt = 30.47 kVAR

St = 170.4 kVA

Meas Time: 00:00:00

Meas

Meas

ChgP Meas

Example of screen in single-

phase mode

Example of screen in “3 wires”

three-phase mode

Example of screen in “4 wires”

three-phase mode


The symbols used are described in Tab. 4.
For eventual messages displayed see Appendix 1

– MESSAGES DISPLAYED.

Following keys are enabled:

F2:

to start / stop immediately a direct energy measurement. The energy
counters will start increasing proportionally to the active power
absorbed by the load.
The results obtained cannot be memorized.
If the active power is negative the counters will not increase.

F1:

(only for 4 wires measurement) to display the following screen. On the
basis of the settings made as per paragraph 5.2 following screens are
displayed cyclically:


Overall three-phase values, values of phase 1, phase 2 and phase 3

SAVE:

to save in the instrument memory a record of “Smp” type (see
paragraph 5.4) containing the instantaneous values of voltage and
current present on the instrument inputs. This function is disabled
during a recording.

ENTER/HOLD: to enable/disable the HOLD function (updating interruption) of the

displayed data. All the previous functions remain however available.
When the HOLD function is enabled, the word

HOLD

is displayed.

When this function is enabled it’s not possible to record or take an
energy measurement. This function is disabled during a recording or
an energy measurement.

MENU:

to enter in the MENU mode and change the instrument settings (see
paragraph 5.2 and 5.3

). It’s not possible to enter the configuration

MENU during a recording or an energy measurement.

START/STOP: to record selected parameters

according to the instrument’s settings

(see chapter 7).

Advertising