Q

Meter/Installation Data

Enter the Numerator and Denominator for each instrument transformer. For example, a PT with a ratio
of 7200/120 has a numerator or 7200, a denominator or 120 and a multiplier of 60 ( 7200/120 = 60/1).

Q

Base Conversion Factors

For Transformer Voltage, enter the Phase-to-Neutral value of Test Voltage previously calculated. For
Transformer Current, enter the Full-Load Current previously calculated. For Multipliers, enter the PT
and CT multipliers previously calculated.
TrfIT Secondary is the Base Value of Voltage and Current at the Instrument Transformer Secondary of
the Power Transformer. These numbers are obtained by dividing the Transformer Voltage and Current
by their respective Multipliers. The Meter/Trf values for Voltage and Current are obtained by dividing
the Meter Base values by the TrfIT Secondary values.

Q

Load Loss at Transformer

No-Load Loss Watts (kW) = 1-Phase kW No-Load Loss = ______________

No-Load Loss VA (kVA)

= (%Exciting Current) * (1-Phase kVA Self-Cooled Rating) / 100

= (______________) * (________________) / 100

= _______________ kVA

No-Load Loss VAR (kVAR)

= SQRT((No-Load Loss kVA)

2

- (No-Load Loss kW)

2

)

= SQRT((_________________)

2

- (________________)

2

)

= SQRT((__________________) - (_________________))

= SQRT (_________________)

= ____________________

Instrument Transformers

Numerator

Denominator

Multiplier

Potential Transformer

Current Transformer

Power Multiplier [(PT Multiplier) times (CT Multiplier)]

Meter Secondary Voltage (volts)

120

Meter Secondary Current (amps)

5

Quantity

Voltage

Current

Transformer

Multiplier

Trf IT Sec

Meter Base

Meter/Trf

120

5