Electro Industries/GaugeTech

Doc # E107706 V1.25

7-7

Full-Load Loss Watts (kW) = 1-Phase Kw Load Loss = ______________

Full-Load Loss VA (kVA)

= (%Impedance) * (1-Phase kVA Self-Cooled Rating) / 100

= (______________) * (________________) / 100

= _______________ kVA

Full-Load Loss VAR (kVAR)

= SQRT((Full-Load Loss kVA)

2

- (Full-Load Loss kW)

2

)

= SQRT((_________________)

2

- (________________)

2

)

= SQRT((__________________) - (_________________))

= SQRT (_________________)

= _________________

Q

Normalize Losses to Meter Base

Enter Value at Transformer Base for each quantity from calculations above. Enter Meter/Trf Factor
value from Base Conversion Factor calculations above. Calculate M/T Factor with Exponent by raising
the M/T Factor to the power indicated in the “Exp” (or Exponent) column.
Calculate the “Value at Meter Base” by multiplying the (M/T Factor w/ Exp) times the (Value at Trf
Base).

Q

Loss Watts Percentage Values

Meter Base kVA

= 600 * (PT Multiplier) * (CT Multiplier) / 1000

= 600 * (____________) * (___________) / 1000

= ________________

Quantity

No-Load Loss kW

Value at Trf

Base

M/T

Factor

M/T Factor

Value

V

V

I

I

Exp

M/T Factor w/

Exp

Value at

Meter Base

No-Load Loss kVAR

Load Loss kW

Load Loss kVAR

∧2
∧4
∧2
∧2