Measurement Procedure
1. Original Signal with amplitude variations.
2. Square demodulator.
3. Weighted filter.

4. Low pass filter 1

st

order.

5. Statistical computing.

Q

Data available

Pst, Pst Max, Pst Min values for long term recording
Plt, Plt Max, Plt Min values for long term recording

Figure 12.1: Simulation of Eye Brain Response

12.3: Setup

Initially the user must set up several parameters to properly configure Flicker. Using Communicator
EXT, from the Icon Menu select Edit Device Profile. From the Device Profile, select Flicker
Settings. The following screen will appear:

Electro Industries/GaugeTech

Doc # E107706 V1.25

12-3

Block 1

Block 2

Block 3

Voltage

Detector

and Gain

Control

Input

Voltage

Adaptor

Square

Law

Demodulator

High Pass

Filter

(DC

Removal)

Low

Pass Filter

(Carrier

Removal

Weighting

Filter

Squaring
Multiplier

1st

Order

Sliding

Mean

Filter

A/D

Converter

Sampling

Rate

>50Hz

Minimum

64 level

Classifier

Output

Interface

Programming of short and

long observation periods

Block 4

Block 5

Simulation Of Eye Brain Response

Output Recording

Instantaneous Flicker in

Perceptibility Units

(Pinst)

Output and Data Display

Pst Max/Min Pst

Plt Max/Min Plt