Factory settings and reset button – Electro-Voice 1252 User Manual

Page 118

Advertising
background image

Electro Industries/GaugeTech

Doc # E107706 V1.25

9-6

NOTE: The PB1 can also be used for a Low Voltage Power Supply. It must be mounted
separately.

5. Once you have combined all the I/O modules together for the group, fasten tightly.

This final tightening will lock the whole group together as a unit.

6. Attach the right Mounting Bracket to the right side of the group using small phillips head screws

provided.

7. Then, mount the group of modules on a secure, flat surface. This procedure will ensure that all

modules stay securely connected.

9.4: Factory Settings and Reset Button

Q

Factory Settings:
All Nexus I/O Modules are shipped with a preset address and a baud rate of 57600. See below for
addresses.

Q

Reset Button:
If there is a communication problem or if you are unsure of a module’s address and baud rate, press
and hold the RESET button for 3 seconds; the module will reset to a default address of 247 at 57600
baud rate for 30-seconds
. This will enable you to interrogate the I/O using the Communicator EXT
software; see the Modbus Communicating I/O Modules User Manual.

Model #

Module

Factory-Set Address

1mAON4

0±1mA, 4-Channel Analog Output

128

1mAON8

0±1mA, 8-Channel Analog Output

128

20mAON4

4–20mA, 4-Channel Analog Output

132

20mAON8

4–20mA, 8-Channel Analog Output

132

8AI1

0±1mA, 8-Channel Analog Input

136

8AI2

0±20mA, 8-Channel Analog Input

140

8AI3

0±5Vdc, 8-Channel Analog Input

144

8AI4

0±10Vdc, 8-Channel Analog Input

148

4RO1

4 Latching Relay Outputs

156

4PO1

4 KYZ Pulse Outputs

160

8DI1

8 Digital Status Inputs (Wet/Dry)

164