2.9: Nexus 1250/1252 Meter Specifications

Specification

Nexus Meter

Control Power Requirements

Option D: 24V DC (-20%) – 48V DC (+20%)

Option D2: 120V AC/DC (-20%) – 230V AC (+20%)

Input Voltage Range

150 Volts Phase to Neutral (Standard; for use with PTs)

300 Volts Phase to Neutral (Option -G)

Input Current Range

10A Maximum (Programmable to any CT Ratio)

Surge Withstanding Per IEEE C37.90.1

Burden

Voltage: 0.05VA @ 120V rms

Current: 0.002VA @ 5A rms

I/O Isolation

2500V DC, 60 Hz

Sensing Method

RMS

Update Time

90 msec

Frequency Range

Fundamental 20–65 Hz

Up to 83rd Harmonic Measuring Capability

Dimensions (HxWxL)

3.4 x 7.3 x 10.5 inches / 8.6 x 18.5 x 26.6 centimeters

Maximum Power Consumption

40 watts (with optional modules and display)

Nominal Power Consumption

Approximately 12 watts (without optional modules and display)

Operating Temperature

-40°C to +80°C / -40°F to +176°F

Auxiliary Output Power Voltage

15–20 V DC at 50–200mA

Maximum Auxiliary Power Current

1.6A (short protected)

Current: Continuous 200% Rated

Current: Surge 10x maximum input for 3 seconds

Input Withstanding Capabilities

UL Listing

1244*

*Not evaluated for accuracy, reliability or capability to perform intended function

.

Flicker (1252)

Evaluation per IEC 61000-4-15