Networking groups of nexus meters – Electro-Voice 1252 User Manual

Page 75

Advertising
background image

Electro Industries/GaugeTech

Doc # E107706 V1.25

5-17

Nexus

Nexus

Nexus

Nexus

Nexus

Nexus

Nexus

Nexus

Nexus

Nexus

Maximum 31 Nexus 1250/1252 Meters, RS-485

Maximum 31 Nexus Meters, RS-485

Maximum 31

Repeaters

Figure 5.15: Networking Groups of Nexus Meters

5.15: Networking Groups of Nexus Meters

You may connect up to 31 Nexus 1250/1252 Meters on the same RS-485 bus. Each one must be
assigned a unique address; see the Communicator EXT User Manual. Use an RS-485 repeater to
network several links of instruments.

A maximum number of 31 Nexus 1250/1252 Meters may be connected to one repeater. A
maximum number of 31 repeaters may be included on the same network.

REPEATER

REPEATER

RS-485/232

Converter