Electro Industries/GaugeTech

Doc # E107706 V1.25

9-7

9.5: Analog Transducer Signal Output Modules

9.5.1: Overview

Q

The Analog Transducer Signal Output Modules (0±1mA or 4–20mA) are available in either a 4- or
8-channel configuration. Maximum registers per request, read or write, is 17 registers.

Q

Nexus 1250/1252 Unit supplies power for up to two connected Analog Output modules. See
section 9.2 for power and communication details. Refer to sections 5.12 - 5.13 to determine if you
must use an additonal power source, such as the EIG PSIO.

Q

All outputs share a single common point. This is also an isolated connection (from ground).

Analog Transducer Signal Output Modules Specifications

Accuracy

Communication

Power Requirement

Operating Temperature

Maximum Load Impedance

RS-485, Modbus RTU

15–20Vdc at 50–200mA;

Nexus 1250/1252 Unit

supports up to 2 Modules

(-20 to 79)°C / (-4 to +158)°F

0±1mA: 10k

Ω; 4–20mA: 500 Ω

Model Numbers

1mAON4: 4-Channel Analog Output, 0±1mA

1mAON8: 8-Channel Analog Output, 0±1mA

20mAON4: 4-Channel Analog Output, 4–20mA

20mAON8: 8-Channel Analog Output, 4–20mA

Factory Settings

Modbus Address:

1mAON4, 0-1mA: 128 1mAON8, 0-1mA: 128

20mAON4, 4–20mA: 132, 20mAON8, 4-20mA: 132

Baud Rate: 57600

Default Settings

(Reset Button)

Modbus Address: 247

Baud Rate: 57600

Programmable Baud Rates: 4800, 9600, 19200, 57500

0.1% of Full Scale

Scaling

Programmable

Transmit Delay Time: 0

Transmit Delay Time: 20 csec