Analog input modules, Overview – Electro-Voice 1252 User Manual

Page 121

Advertising
background image

Electro Industries/GaugeTech

Doc # E107706 V1.25

9-9

Default Settings

(Reset Button)

9.6: Analog Input Modules

Analog Input Modules Specifications

Model Numbers

8AI1: 8-Channel Analog Input, 0±1mA

8AI2: 8-Channel Analog Input, 0±20mA

8AI3: 8-Channel Analog Input, 0±5Vdc

8AI4: 8-Channel Analog Input, 0±10Vdc

Accuracy

0.1% of Full Scale

Scaling

Programmable

Communication

RS-485, Modbus RTU

Programmable Baud Rates: 4800, 9600, 19200,57600

Power Requirement

15-20Vdc at 50-200mA;

Nexus 1250/1252 Unit

supports up to 4 Modules

Operating Temperature

(-20 to 79)°C / (-4 to +158)°F

Maximum Load

Impedance

0-1mA: 10k

Ω; 4-20mA: 500 Ω

Factory Settings

Modbus Address:

8AI1, 0±1mA: 136; 8AI2, 0±20mA: 140

8AI3, 0±5Vdc: 144, 8AI4, 0±10Vdc: 148

Baud Rate: 57600

Modbus Address: 247

Baud Rate: 57600

9.6.1: Overview

Q

The Analog Input Modules (0±1mA, 0±20mA, 0±5Vdc and 0±10Vdc) are available in 8-channel
format. Maximum registers per request, read or write, is 17 registers.

Q

Nexus 1250/1252 Unit supplies power for up to 4 connected Analog Input modules. See section 9.2
for power and communication details. Refer to sections 5.12 - 5.13 to determine if you must use an
additonal power source, such as the EIG PSIO.

Q

All inputs share a single common point. This is also an isolated connection (from ground).

Transmit Delay Time: 0

Transmit Delay Time: 20 csec

Advertising
This manual is related to the following products:

250