Three element loss compensation worksheet – Electro-Voice 1252 User Manual

Page 107

Advertising
background image

Electro Industries/GaugeTech

Doc # E107706 V1.25

7-5

7.2.1.1: Three Element Loss Compensation Worksheet

Q

Transformer Data (from Transformer Manufacturer’s Test Sheet)

Enter 3-Phase or 1-Phase values. If 3-Phase values are entered, calculate 1-Phase values by dividing
3-Phase values by three. Convert 1-Phase Loss Watts to 1-Phase kW by dividing 1-Phase Loss Watts by
1000.

Enter 3-Phase or 1-Phase values. If 3-Phase values are entered, calculate 1-Phase values by dividing
3-Phase values by three. Convert 1-Phase Self-Cooled MVA to 1-Phase kVA by multiplying by 1000.

Test Voltage is generally Phase-to-Phase for three-phase transformers. Calculate Phase-to-Neutral
Voltage by dividing Phase-to-Phase Voltage by

√3. Calculate Full Load Current by dividing the (1-Phase

kW Self-Cooled Rating) by the (Phase-to-Neutral Voltage) and multiplying by 1000.

Company

Date

Trf Manf

Calculation by

Station Name

Trf Bank No.

Trf Serial No.

Connection

Winding

Voltage

MVA

HV - High

∆ - Y

Xv - Low

YV - Tertiary

∆ - Y
∆ - Y

Watts Loss

1-Phase

3-Phase

1-Phase kW

Value

No-Load Loss

Load Loss

Value

3-Phase MVA

1-Phase MVA

1-Phase kVA

Self-Cooled Rating

% Exciting Current

% Impedance

Value

Phase-to-Phase

Phase-to-Neutral

Test Voltage (volts)

Full Load Current (Amps)