9.7: Digital Dry Contact Relay Output (Form C) Module

Digital Dry Contact Relay Output (Form C) Module Specifications

Model Number

Communication

Power Requirement

Operating Temperature

Maximum Load Impedance

4RO1: 4 Latching Relay Outputs

RS-485, Modbus RTU

Programmable Baud Rates: 4800, 9600, 19200, 57600

15–20Vdc at 50–200 mA;

Nexus 1250/1252 Unit

supports up to 4 Modules

(-20 to 79)°C / (-4 to +158)°F

0-1mA: 10k

Ω; 4-20mA: 500 Ω

Factory Settings

Modbus Address: 156

Baud Rate: 57600

Default Settings

(Reset Button)

Modbus Address: 247

Baud Rate: 57600

9.7.1: Overview

Q

The Relay Output Module consists of four Latching Relay Outputs. In Normal Mode, the device
accepts commands to control the relays. Relay output modules are triggered by limits programmed
with the Communicator EXT software. See the Communicator EXT User Manual for details on
programming limits.

Q

Nexus 1250/1252 Unit supplies power for up to 4 connected Relay Output modules. See section 9.2
for power and communication details. Refer to sections 5.12 - 5.13 to determine if you must use an
additonal power source, such as the EIG PSIO.

Q

The Modbus Map for the Analog Output Module (and operating details) can be found in the Modbus
Communicating I/O Modules Manual.

Q

Each latching relay will hold its state in the event of a power loss.

Transmit Delay Time: 0

Transmit Delay Time: 20 csec

Programmable

Accuracy

Scaling

0.1% of Full Scale