3.4: Mounting the Nexus External I/O Modules

Q

Secure the mounting brackets to the I/O using the screws supplied (#440 pan-head screws). Next,
secure the brackets to a flat surface using a #8 screw with a lock washer.

Q

If multiple I/O modules are connected together, as shown in Figure 3.4, secure a mounting bracket to
both ends of the group. One Nexus will supply power for up to four I/O modules. To connect more
than four I/O modules, use an additional power supply, such as the EIG PSIO. Connect multiple I/O
modules using the RS-485 side ports.

Q

Six feet of RS-485 cable harness is supplied. The cable harness brings power to the display from the
Nexus Meter, which supplies 15–20V DC at 50–200mA. See Chapter 5 for power supply and com-
munication details.

Figure 3.7: Nexus I/O Modules Mounting Diagram, Overhead View

Mounting Bracket

Mounting Bracket

Figure 3.8: Nexus I/O Module Communication Ports

Female RS-485 Side Port

I/O Port

Mounting Brackets (MBIO)

0.015” (.38mm)

1.125” (2.85cm)

2 x .625” (1.58cm)

4.215” (10.70cm)

Male RS-485 Side Port