5.12: Steps to Determine Power Needed

Available power for All Ports of the Nexus 1250/1252 is 12 VA.

Refer to the table below to determine the VA Ratings for I/O modules and displays.

Add together the VA Ratings for I/Os and Displays in use.

Compare Available Power to Power Needed to determine if you must use an additional

power source. EIG recommends the PSIO 12V power source. See section 9.2.1.

5.13: I/O Modules’ Factory Settings and VA Ratings

All I/Os are shipped pre-programmed with a baud rate of 57600 and addresses. The table below
details the factory-set address for each module and the VA Ratings for I/O modules and Nexus
displays. Refer to the previous section (section 5.12) for the steps to determine if you must use an
additional power source. For programming, refer to Chapter 8 of the Communicator EXT User
Manual.

I/O MODULES’ FACTORY SETTINGS AND VA RATINGS

MODEL NUMBER

1mAON4

1mAON8

20mAON4

20mAON8

8A11

8A12

8A13

8A14

4RO1

4PO1

8D11

MODULE

0-1mA, 4 Analog Outputs

0-1mA, 8 Analog Outputs

4-20mA, 4 Analog Outputs

4-20mA, 8 Analog Outputs

0-1mA, 8 Analog Outputs

0-20mA, 8 Analog Outputs

0-5V DC, 8 Analog Outputs

0-10V DC, 8 Analog Outputs

4 Latching Relay Outputs

4 KYZ Pulse Outputs

8 Status Inputs (Wet/Dry)

NEXUS DISPLAYS’ VA RATINGS

ADDRESS

VA RATING

128

2.7 VA

128

3.2 VA

132

5.0 VA

132

8.5 VA

136

2.3 VA

140

2.3 VA

144

2.3 VA

148

2.3 VA

156

2.7 VA

160

2.7 VA

164

1.0 VA

P40N, P41N or P43N

P60N

Nexus LED Display

Nexus Touch Screen Display

8 VA

5 VA