Instruction Bulletin

Appendix J Rev. 1.2

May 2005

Rosemount Analytical Inc. A Division of Emerson Process Management

Appendices J-3

World Class 3000

INSTALLATION

J-4

HART COMMUNICATOR SIGNAL LINE
CONNECTIONS

The HART Communicator can connect to the
IFT analog output signal line at any wiring ter-
mination point in the 4-20 mA current loop.
There are two methods of connecting the HART
Communicator to the signal line. For applica-
tions in which the signal line has a load resis-
tance of 250 ohms or more, refer to method 1.

For applications in which the signal line load re-
sistance is less than 250 ohms, refer to
method 2.

a. Method 1, For Load Resistance > 250

Ohms

Refer to Figure J-2 and the following steps
to connect the HART Communicator to a
signal line with 250 ohms or more of load
resistance.

INTELLIGENT FIELD
TRANSMITTER IFT 3000

J1

JM1

J2

J3

J4

J5

J6

J7

J8

J9

LOOP

CONNECTORS

O 4-20 MA SIGNAL LINE

2

HART

COMMUNICATOR

MODEL 275/375

ANALOG OUTPUT DEVICE

HART COMMUNICATOR

REAR PANEL

JM8

3D39513G, REV 13

MICROPROCESSOR

BOARD

10

J1

JM6

J2

J3

SW2

SW3

A

B

C

D

ON

OFF

37840018

LEAD SET

RL 250

>

MICROPROCESSOR

BOARD

CURRENT/VOLTAGE SELECTION SWITCH
TO "CURRENT" POSITION

INTERCONNECT BOARD

ANALOG OUTPUT

Figure J-2. Signal Line Connections, > 250 Ohms Load Resistance