Installation and setup guide 2-12 – Honeywell VISTA-20P User Manual

Page 18

Advertising
background image

On-Board Triggers

Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally
located above the terminal strip.
• If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1

cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for
transformer connections.

• If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied

with the control) as shown below.

1

3

4

5

6

7

8

SA412OXM-1
CABLE

8-PIN TRIGGER CONNECTOR

KEY

00-trigcon-003-V1

+12 A

UX.

D

ATA

COM

SYNC

GND (-)

OUTPUT 17

(RED)

OUTPUT 18

(GREEN)

(ORANGE)

(YELLO

W)

(BLUE)

(PURPLE)

(BLA

CK)

4-WIRE
CABLE

00-trigcon-005-V2

+12 A

UX.

GND (-)

OUTPUT 17

OUTPUT 18

(RED)

(YELLO

W)

(BLA

CK)

(GREEN)

1

3

4

5

6

7

8

8-PIN TRIGGER CONNECTOR

KEY

Figure 15a. On-Board Trigger Connector

Figure 15b. On-Board Trigger Connector

with SA4120XM-1 Cable for Use With

with 4-Wire Cable for Trigger Use Only

1361X10 Transformer

• Trigger outputs are normally high, and go low upon programmed condition.

• The outputs can be programmed for inverted operation (normally low, go high) using

*79 Menu mode.

• Program these triggers using *80/*81 Menu modes as you would for any other relay

output.

• When using these outputs, note:

pin 1 = output number 17 (trigger 1):

15 ohms to ground when closed (output low), open when off (output high, normal
default); can be used to reset smoke detector power (must set “output normal low
= yes” in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu
mode); or can support 12V relay module (

e.g., Altronix AX-RBS)

that draws less

than 100mA

pin 5 = output number 18 (trigger 2):

100 ohms to ground when closed (output low); open when off (output high,
normal default); or can support 12V relay module that draws less than 20mA

UL

If on-board triggers are used, the wiring between the control unit and the UL Listed device must

be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.

Installation and Setup Guide

2-12