Various system trouble displays – Honeywell VISTA-20P User Manual

Page 61

Advertising
background image

Various System Trouble Displays

Alpha Display

Fixed Disp.

Meaning

ALARM CANCELED

CA

will appear if an exit or interior zone contained a fault during closing at the
time the Exit Delay ended (e.g., exit door left open), but the system was
disarmed during the Entry Delay time. The alarm sounder and keypad sound
continuously, but stop when the system is disarmed. No message will be
transmitted to the central station.

EXIT ALARM

EA

appears when Exit Delay ends if an exit or interior zone contained a fault
during closing. The alarm sounder and keypad sound continuously until the
system is disarmed (or timeout occurs). An “Exit Alarm” message is sent to the
central station. Also results if an alarm from an exit or interior zone occurs
within 2 minutes after the end of an Exit Delay.

CHECK CHECK

indicates that a problem exists with the displayed zone(s) and requires
attention.

ALARM 1xx
FAULT 1xx
CHECK 1xx

1xx
1xx
1xx
91

indicates that communication between control and a zone expander or wireless
receiver is interrupted, where “xx” is the device address. Check the wiring and
DIP switch settings on the units.
If field *199 is set to “1,” all ECP module problems are displayed as “91.”
If there are wireless sensors in the system, the Check condition may also be
caused by some change in the environment that prevents the receiver from
receiving signals from a particular sensor.

SYSTEM LO BAT

BAT

with no zone number indicates that the system's standby battery is weak.

LO BAT

BAT

with a zone number and a once-per-minute beeping at the keypad indicates
that a low-battery condition exists in the wireless sensor displayed (zone “00”
indicates a wireless keypad). If the battery is not replaced within 30 days, a
“CHECK” display may occur.
NOTE: Some wireless sensors contain a non-replaceable long-life battery which
requires replacement of the entire unit at the end of battery life (e.g., Nos.
5802, 5802CP).

TELCO FAULT

94

Telephone Line Failure, indicates that a monitored telephone line (if
programmed in field *92) has been cut or disconnected. Depending on how the
system was programmed, the keypad may also produce a trouble sound, and
the external sounder may be activated. Silence by entering installer code +
OFF.

Busy-Standby dl

If this remains displayed for more than 1 minute, the system is disabled.

Mode m Comm

CC

The system is in communication with the central station for change of function
or status verification.

no display

no display

Power Failure
If there is no keypad display at all and the LEDs are unlit, operating power
(AC and battery) for the system has stopped and the system is inoperative.
If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word
display keypads) is displayed, the keypad is operating on battery power only.
If the battery standby capacity is used up during a prolonged AC power outage,
the control's power will shut down to minimize deep discharge of the battery.

Comm. Failure

FC

A communication failure has occurred.

Open Circuit

OC

The keypad is not receiving signals from the control; sees an open circuit.

Long Rng Trbl

bF

Backup LRR communication failure.

Bell Failure

70

Bell supervision failure.

RCVR Jam

90

RF jam detected.

KEYPAD LOW BAT

00 BAT

Wireless keypad low battery.

Phone Okay

Cd

The dialer test has been successful (CID code 601).

Dialer Off

dO

The dialer is disabled.

Test in Progress

dd

Walk test mode is active(CID code 607).

Upload Completed

dC

The upload or download session was completed.

Upload Failed

dF

The upload or download session failed before completion.

System Operation

6-7

Advertising
This manual is related to the following products: