Auxiliary device current draw worksheet, Installation and setup guide 2-2, Figure 3. mounting the pc board and rf receiver – Honeywell VISTA-20P User Manual

Page 8

Advertising
background image

ANTENNA

MOUNT

(2 PLACES)

ANTENNA

(2)

SCREW

(2)

BLACK

MOUNTING

CLIP

RED

MOUNTING

CLIP

WHITE

MOUNTING

CLIP

GROUNDING

LUG

(2)

NOTE
A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN
INCLUDED IN YOUR INSTALLATION KIT.
USE THE APPROPRIATE CLIPS FOR MOUNTING.

IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING
EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE
INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.

DETAIL A

SIDE VIEW

OF BOARD -

SUPPORTING SLOTS

CIRCUIT

BOARD

CABINET

MOUNTING
CLIP

CABINET

MOUNTING
CLIP

CONTROL

CIRCUIT

BOARD

BOARD
SUPPORTING
SLOTS

RECEIVER CIRCUIT BOARD

+

+

A

B

pc_mount-001-V1

DETAIL B

ANTENNA AND GROUNDING

LUG INSTALLATION

INSTALLATION WITH RECEIVER CIRCUIT BOARD

Figure 3. Mounting the PC Board and RF Receiver

AUXILIARY DEVICE CURRENT DRAW WORKSHEET

DEVICE

CURRENT

No. UNITS

TOTAL CURRENT

6150 Fixed-Word Keypad

40mA/70mA**

6160 Alpha Keypad

40mA/150mA**

6150V Fixed-Word Display Voice Keypad

60mA/160mA**

6160V Alpha Display Voice Keypad

60mA/190mA**

8132/8142 Series AUI (Symphony)

150mA/400mA**

6270 Touch Screen Keypad

180mA/280mA**

5881/5882 RF Receiver

60mA

5883 Transceiver

80mA

4219 Zone Expander

30mA

4204 Relay Unit

15/180mA‡

4229 Zone Expander/Relay Unit

30/100mA‡

4285 Phone Module

160mA

4286 Phone Module

300mA

*

(Current available from Aux. terminals = 600 mA max.)†

TOTAL =

*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw.

** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on

†In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output).

‡Values are for relays OFF/relays ON.

CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE

24-HOUR BATTERY BACKUP REQUIREMENTS

The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be
provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in
the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can
meet these requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output
currents are limited as indicated below.

OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES

OUTPUT CURRENT LIMITATIONS

BATTERY INFORMATION

Output Current Total

Maximum Auxiliary Current

Battery Capacity

To Use (Amp/Hrs)

Recommended Battery

(Yuasa Model No.)

600mA maximum total of

auxiliary power plus bell

output currents

45mA

160mA
200mA
425mA
500mA

4AH
7AH
8AH

14AH

17.2AH

NP4-12 (or ADEMCO 467)

NP7-12
NP4-12 (two) ‡
NP7-12 (two) ‡
NPG18-12

NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the cabinet.)

Installation and Setup Guide

2-2