Device output number, Output normally low, Output type – Honeywell VISTA-20P User Manual

Page 45: Unit number, Module address, Relay position, Menu mode programming 5-9

Advertising
background image

Start Output Device Mapping by pressing *79 while in Data Programming Mode.

∗∗∗∗79 Menu Mode

ENTER OUTPUT NO.

00 = QUIT

xx

Device Output Number

01-18 = VISTA-20P relays/X-10; 01-08, 17, 18 = VISTA-15P relays/X-10
[

∗] to continue; 00 to quit

This is the logical (or reference) relay number as used in the system. Relays and X-10
devices are numbered 01-16; the on-board triggers are numbered 17 and 18 and can be
programmed for inverted output, if required. Use the worksheet on the Programming Form
(printed separately) to organize device numbers.

17 OUT NORM LOW

0 = NO 1 = YES

0

Output Normally Low

(prompt appears only for Triggers 17 and 18)

0 = no (standard default); 1 = yes
[

∗] to continue

Selecting 0 (no) sets the output level normally high (default setting).
Selecting 1 (yes) sets the output normally low.
Output Trigger 17 can be used for resetting 4-wire smoke detectors by connecting it to the
negative power terminal of the smoke detector, selecting 1 at this prompt, and setting as
zone type 54, fire zone reset, in *80 Menu mode.
After entry, display returns to Output Number prompt. Use *80 Menu mode to program
the function of the trigger.

XX OUTPUT TYPE

DELETE 0

Output Type

0 = delete; 1 = relay on 4204/4229 module; 2 = Powerline Carrier device (X-10)
[

∗] to continue

Select whether this is a relay or a Powerline Carrier (X-10) device.
If Powerline Carrier is selected, go to “A” prompt.
If relay is selected, skip to “B” prompt.

“A”

XX UNIT No.

yy

Unit Number

(prompt appears

if X-10 is selected)

01-16 = predefined address
[

∗] to continue

Enter the unit code (set at the device) and press [

∗].

The system returns to the Output Number prompt.

“B”

XX MODULE ADDR

07-15 yy

Module Address

(prompt appears

if relay is selected)

07-15 = predefined address
[

∗] to continue

Enter the predefined address for this module as listed below. Make sure the module’s DIP
switches are set to the selected address.
Module Addresses

Address Module

† These addresses apply to VISTA-20P only.

07

1st 4229 (with zones 09-16)

08

2nd 4229 (with zones 17-24)

09

3rd 4229 (with zones 25-32)

10

4th 4229 (with zones 33-40)

11

5th 4229 (with zones 41-48)

12

1st 4204

13

2nd 4204

14

3rd

4204

15

4th

4204

XX REL POSITION

1-4 zz

Relay Position

1-4 = relay position
[

∗] to continue

This is the actual (or physical) relay number with respect to the Relay Module upon which
it is located. For 4204 modules, relay numbers are 1-4. For 4229 modules, relay numbers
are 1-2.
The system returns to the Output Number prompt for programming the next device.

Menu Mode Programming

5-9