Ademco Contact ID

®

The Ademco Contact ID

®

Reporting Format comprises the following:

4-digit or 10-digit subscriber number (depending on format selected).
1-digit event qualifier (“new” or “restore”).
3-digit event code.
2-digit Partition No.
3-digit zone number, user number, or system status number (see the following page).

Ademco Contact ID

®

Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ

where:

CCCC(CCCCCC) =Customer (subscriber) ID

Q = Event qualifier, where:

E = new event , and R = restore

EEE = Event code (3 hexadecimal digits)

Note: For a complete list of event codes, refer to the central office

receiver manual.

GG = Partition Number (system messages show “00”)

ZZZ = Zone/contact ID number reporting the alarm, or user number for

open/close reports. System status messages (AC Loss, Walk Test, etc.)
contain zeroes in the ZZZ location.

TABLE OF CONTACT ID EVENT CODES

(some event codes may not apply to certain control panels)

Code

Definition

110 Fire

Alarm

121 Duress
122 Alarm,

24-hour

Silent

123

Alarm, 24-hour Audible

131 Alarm,

Perimeter

132 Alarm,

Interior

134 Alarm,

Entry/Exit

135 Alarm,

Day/Night

143

Alarm, Expansion Module

145 ECP

Module

cover

tamper

146 Silent

Burglary

150

Alarm, 24-Hour Auxiliary/Monitor zone

162 Carbon

Monoxide

301 AC

Power

302

Low System Battery/Battery Test Fail

305

System Reset (Log only)

309

Battery Test Failure

321 Bell/Siren

Trouble

333

Trouble, Expansion Mod. Supervision

341

Trouble, ECP Cover Tamper

344 RF

Receiver

Jam

351

Telco Line Fault

353

Long Range Radio Trouble

373

Fire Loop Trouble

374

Exit Error Alarm

380

Global Trouble, Trouble Day/Night

Code Definition

381

RF Sensor Supervision

382

Supervision Auxiliary Wire Zone

383

RF Sensor Tamper

384

RF Sensor Low-battery

393 Clean

Me

401

Disarmed, Armed AWAY, Armed
MAXIMUM

403

Schedule Arm/Disarm AWAY

406

Cancel by User

407

Remote Arm/Disarm (Downloading)

408

Quick Arm AWAY

409

Keyswitch Arm/Disarm AWAY

441 Disarmed/Armed

STAY/INSTANT,

Quick-Arm STAY/INSTANT

442

Keyswitch Arm/Disarm STAY

459 Recent

Closing

570 Bypass
601

Manually Triggered Dialer Test

602

Periodic Test

606

AAV to Follow

607

Walk Test Entered/Exited

623

Event Log 80% Full

625

Real-Time Clock was Changed (log only)

627

Program Mode Entry (log only)

628

Program Mode Exit (log only)

642

Latch Key (log only)