Heat & Glo • 6000G, 6000G-IPI • 2103-900 Rev. M • 9/08

14

Figure 5.5

1. Top Vent - Horizontal Termination - (continued)

Three Elbows

V

1

Min.

H

1

Max.

V

2

Min.

H

2

Max.

Elbow only

2 ft.

610 mm

0 in.

0 mm

1 ft.

305 mm

6 in.

152 mm

3 ft

914 mm

6 in.

152 mm

2 ft.

610 mm

1 ft.

305 mm

6 ft.

1.8 m

1 ft.

305 mm

6 ft.

1.8 m

2 ft.

610 mm

11 ft.*

3.4 m*

2 ft.

610 mm

10 ft.*

3.1 m*

3 ft.

914 mm

16 ft *

4.9 m*

3 ft.

914 mm

14 ft.*

4.3 m*

*H

1

+ H

2

= 20 ft. (6.1 m) Maximum V

1

+ V

2

+ H

1

+ H

2

= 40 ft. (12.2 m) Maximum

Fire Risk.
• When using DVP-HRC-SS and DVP-HRC-ZC-

SS termination caps on top vented fi replaces, a
6 inch minimum vertical vent section is required
before installing fi rst elbow.

WARNING